-40%
Honeywell S89F 1098 Direct Spark Gas Burner Primary S89F1098 Brand New
$ 52.96
- Description
- Size Guide
Description
Template By Froo!Honeywell S89F 1098 Direct Spark Gas Burner Primary S89F1098 Brand New
Honeywell S89F1098
***PLEASE NOTE***
We Buy These In Bulk From a Burner Manufacturer. They are Bulk Packed and Do Not Come With Boxes or Instructions. You Will Get Exactly What Is Pictured Brand New.
2 Rod Direct Spark Ignition Control,4/4 Time
Product Specifications
Dimensions (in.)
5 1/4 in. high x 4 1/16 in. wide x 1 15/16 in. long
Dimensions (mm)
133 mm high x 103 mm wide x 49 mm deep
Electrical Ratings
24 Vac
Frequency
60 Hz
Approvals, Canadian Standards Association
Design Certified
Flame Failure Response Time (sec)
2.0 sec. @ 2.5 microamp
PrePurge
30 sec. minimum
Ambient Temperature Range (F)
-40 F to +175 F
Ambient Temperature Range (C)
-40 C to +79 C
Ignition System Type
Direct Spark Ignition
Ignition Sequence
Single trial for main burner ignition (then shut down and lockout)
Typical Gas Control
VR8205, VR8305
Type of Gas
Natural or LP
Flame Sense
Two Rod
Ignition Source
External (120 VAC powered) High Voltage Spark Generator
Ignition Trials To Lockout
1
Lockout Timing
4 sec.
Ignition Trial Time (sec)
4 sec.
Maximum Valve Load @ 24 Vac (Amps)
2A
Flame Failure Re-ignition Time (sec)
0.8 sec. maximum